Arizona Administrative Code (Last Updated: November 17, 2016) |
Title 20. COMMERCE, FINANCIAL INSTITUTIONS, AND INSURANCE |
Chapter 2. DEPARTMENT OF WEIGHTS AND MEASURES |
Article 10. STAGE I VAPOR RECOVERY |
Table 1. Acceptability of Final System Pressure Results for Systems Tested Using TP-201.3
Latest version.
All data is extracted from pdf, click here to view the pdf.
-
Ullage (gallons)
Minimum Pressure after Five Minutes (Inches Water Column)
500
0.73
550
0.80
600
0.87
650
0.93
700
0.98
750
1.03
800
1.07
850
1.11
900
1.15
950
1.18
1000
1.21
1200
1.32
1400
1.40
1600
1.46
1800
1.51
2000
1.56
2400
1.62
2600
1.65
2800
1.67
3000
1.69
3500
1.73
4000
1.76
4500
1.79
5000
1.81
6000
1.84
7000
1.86
8000
1.88
9000
1.89
10000
1.90
15000
1.93
20000
1.95
25000
1.96
Historical Note
Table 1 made by final rulemaking at 21 A.A.R. 1693, effective October 3, 2015 (Supp. 15-3).