Table 1. Unit Design Flows


Latest version.

All data is extracted from pdf, click here to view the pdf.

  •   

    Wastewater Source

      

    Applicable Unit

    Sewage Design Flow per Applicable Unit, Gallons Per Day

    Airport

    Passenger (average daily number)

    4

    Employee

    15

    Auto Wash

    Facility

    Per manufacturer, if consis- tent with this Chapter

    Bar/Lounge

    Seat

    30

    Barber Shop

    Chair

    35

    Beauty Parlor

    Chair

    100

    Bowling Alley (snack bar only)

    Lane

    75

    Camp

      

    Camping unit

      

    30

    Day camp, no cooking facilities

    Campground, overnight, flush toilets

    Camping unit

    75

    Campground, overnight, flush toilets and shower

    Camping unit

    150

    Campground, luxury

    Person

    100-150

    Camp, youth, summer, or seasonal

    Person

    50

    Church

      

    Person (maximum attendance)

      

    5

    Without kitchen

    With kitchen

    Person (maximum attendance)

    7

    Country Club

    Resident Member

    100

    Nonresident Member

    10

    Dance Hall

    Patron

    5

    Dental Office

    Chair

    500

    Dog Kennel

    Animal, maximum occupancy

    15

    Dwelling

    For determining design flow for sewage treatment facilities under R18-9-B202(A)(9)(a) and sewage collection systems under R18-9-E301(D) and R18-9- B301(K), excluding peaking factor.

      

    Person

      

    80

    Dwelling

    For on-site wastewater treatment facilities per R18-9- E302 through R18-9-E323:

    Apartment Building 1 bedroom

    2  bedroom

    3  bedroom

    4  bedroom

      

    Seasonal or Summer Dwelling (with recorded sea- sonal occupancy restriction)

      

    Single Family Dwellings

      

    Other than Single Family Dwelling, the greater flow value based on:

    Bedroom count 1-2 bedrooms

    Each bedroom over 2 Fixture count

      

      

      

      

    Apartment Apartment Apartment Apartment

      

    Resident

      

      

    see R18-9-A314(D)(1)

      

      

      

      

    Bedroom Bedroom Fixture unit

      

      

      

      

    200

    300

    400

    500

      

    100

      

      

    see R18-9-A314(D)(1)

      

      

      

      

    300

    150

    25

    Fire Station

    Employee

    45

    Hospital

      

    Bed

      

    250

    All flows

    Kitchen waste only

    Bed

    25

    Laundry waste only

    Bed

    40

    Hotel/motel Without kitchen With kitchen

      

    Bed (2 person)

    Bed (2 person)

      

    50

    60

    Industrial facility

      

    Employee

      

    25

    Without showers

    With showers

    Employee

    35

    Cafeteria, add

    Employee

    5

    Institutions

      

    Person

      

    75

    Resident

    Nursing home

    Person

    125

    Rest home

    Person

    125

    Laundry Self service

    Commercial

      

    Wash cycle Washing machine

      

    50

    Per manufacturer, if consis- tent with this Chapter

    Office Building

    Employee

    20

    Park (temporary use)

      

    Parking space

      

    40

    Picnic, with showers, flush toilets

    Picnic, with flush toilets only

    Parking space

    20

    Recreational vehicle, no water or sewer connections

    Vehicle space

    75

    Recreational vehicle, with water and sewer

    Vehicle space

    100

    connections

     

     

    Mobile home/Trailer

    Space

    250

    Restaurant/Cafeteria

    Employee

    20

    With toilet, add

    Customer

    7

    Kitchen waste, add

    Meal

    6

    Garbage disposal, add

    Meal

    1

    Cocktail lounge, add

    Customer

    2

    Kitchen waste disposal service, add

    Meal

    2

    Restroom, public

    Toilet

    200

    School

    Staff and office Elementary, add Middle and High, add

    with gym & showers, add with cafeteria, add Boarding, total flow

      

    Person Student Student Student Student Person

      

    20

    15

    20

    5

    3

    100

    Service Station with toilets

    First bay

    1000

    Each additional bay

    500

    Shopping Center, no food or laundry

    Square foot of retail space

    0.1

    Store

    Employee

    20

    Public restroom, add

    Square foot of retail space

    0.1

    Swimming Pool, Public

    Person

    10

    Theater

      

    Seat

      

    5

    Indoor

    Drive-in

    Car space

    10

    Note: Unit flow rates published in standard texts, literature sources, or relevant area or regional studies are considered by the Depart- ment, if appropriate to the project.

Historical Note