Arizona Administrative Code (Last Updated: November 17, 2016) |
Title 18. ENVIRONMENTAL QUALITY |
Chapter 9. DEPARTMENT OF ENVIRONMENTAL QUALITY |
Article 3. AQUIFER PROTECTION PERMITS - GENERAL PERMITS |
Part E. TYPE 4 GENERAL PERMITS |
Table 1. Unit Design Flows
All data is extracted from pdf, click here to view the pdf.
-
Wastewater Source
Applicable Unit
Sewage Design Flow per Applicable Unit, Gallons Per Day
Airport
Passenger (average daily number)
4
Employee
15
Auto Wash
Facility
Per manufacturer, if consis- tent with this Chapter
Bar/Lounge
Seat
30
Barber Shop
Chair
35
Beauty Parlor
Chair
100
Bowling Alley (snack bar only)
Lane
75
Camp
Camping unit
30
Day camp, no cooking facilities
Campground, overnight, flush toilets
Camping unit
75
Campground, overnight, flush toilets and shower
Camping unit
150
Campground, luxury
Person
100-150
Camp, youth, summer, or seasonal
Person
50
Church
Person (maximum attendance)
5
Without kitchen
With kitchen
Person (maximum attendance)
7
Country Club
Resident Member
100
Nonresident Member
10
Dance Hall
Patron
5
Dental Office
Chair
500
Dog Kennel
Animal, maximum occupancy
15
Dwelling
For determining design flow for sewage treatment facilities under R18-9-B202(A)(9)(a) and sewage collection systems under R18-9-E301(D) and R18-9- B301(K), excluding peaking factor.
Person
80
Dwelling
For on-site wastewater treatment facilities per R18-9- E302 through R18-9-E323:
Apartment Building 1 bedroom
2 bedroom
3 bedroom
4 bedroom
Seasonal or Summer Dwelling (with recorded sea- sonal occupancy restriction)
Single Family Dwellings
Other than Single Family Dwelling, the greater flow value based on:
Bedroom count 1-2 bedrooms
Each bedroom over 2 Fixture count
Apartment Apartment Apartment Apartment
Resident
see R18-9-A314(D)(1)
Bedroom Bedroom Fixture unit
200
300
400
500
100
see R18-9-A314(D)(1)
300
150
25
Fire Station
Employee
45
Hospital
Bed
250
All flows
Kitchen waste only
Bed
25
Laundry waste only
Bed
40
Hotel/motel Without kitchen With kitchen
Bed (2 person)
Bed (2 person)
50
60
Industrial facility
Employee
25
Without showers
With showers
Employee
35
Cafeteria, add
Employee
5
Institutions
Person
75
Resident
Nursing home
Person
125
Rest home
Person
125
Laundry Self service
Commercial
Wash cycle Washing machine
50
Per manufacturer, if consis- tent with this Chapter
Office Building
Employee
20
Park (temporary use)
Parking space
40
Picnic, with showers, flush toilets
Picnic, with flush toilets only
Parking space
20
Recreational vehicle, no water or sewer connections
Vehicle space
75
Recreational vehicle, with water and sewer
Vehicle space
100
connections
Mobile home/Trailer
Space
250
Restaurant/Cafeteria
Employee
20
With toilet, add
Customer
7
Kitchen waste, add
Meal
6
Garbage disposal, add
Meal
1
Cocktail lounge, add
Customer
2
Kitchen waste disposal service, add
Meal
2
Restroom, public
Toilet
200
School
Staff and office Elementary, add Middle and High, add
with gym & showers, add with cafeteria, add Boarding, total flow
Person Student Student Student Student Person
20
15
20
5
3
100
Service Station with toilets
First bay
1000
Each additional bay
500
Shopping Center, no food or laundry
Square foot of retail space
0.1
Store
Employee
20
Public restroom, add
Square foot of retail space
0.1
Swimming Pool, Public
Person
10
Theater
Seat
5
Indoor
Drive-in
Car space
10
Note: Unit flow rates published in standard texts, literature sources, or relevant area or regional studies are considered by the Depart- ment, if appropriate to the project.
Historical Note
New Section adopted by final rulemaking at 7 A.A.R. 235, effective January 1, 2001 (Supp. 00-4). Amended by final rulemaking at 11 A.A.R. 4544, effective November 12, 2005 (05-3).