Article 4. ARIZONA BOILERS AND LINED HOT WATER HEATERS |
Section R20-5-401. Applicability
All data is extracted from pdf, click here to view the pdf.
-
This Article applies to all boilers, lined hot water heaters and pres- sure vessels operated in Arizona, except the following:
1. Boilers, lined hot water heaters and pressure vessels regu- lated by the United States Government;
2. Boilers, lined hot water heaters and pressure vessels oper- ated in private residences or apartment complexes of not more than six units; and
3. Boilers, lined hot water heaters and pressure vessels oper- ated on Indian reservations.
4. A lined hot water heater that does not exceed any of the following:
a. Heat input of 200,000 BTU per hour,
b. Water temperature of 210º F, and
c. Nominal water containing capacity of 120 gallons.