Section R20-2-712. Water in Service Station Motor Fuel Storage Tanks  


Latest version.

All data is extracted from pdf, click here to view the pdf.

  • A service station owner or operator shall ensure that water in a ser- vice station motor fuel storage tank other than an alcohol gasoline blend, does not exceed 1” in depth when measured from the bottom through the fill pipe. The service station owner or operator shall remove all water from the tank before delivery or sale of motor fuel from that tank.

Historical Note

Former Section R4-31-204(J) renumbered without change as Section R4-31-712 (Supp. 89-1). Section repealed, new Section adopted effective February 21, 1990 (Supp. 90-1). Amended by emergency action effec- tive September 20, 1991, pursuant to A.R.S. § 41-1026, valid for only 90 days (Supp. 91-3). Emergency amend- ments adopted again without change effective December 20, 1991, pursuant to A.R.S. § 41-1026, valid for only 90 days (Supp. 91-4). Emergency amendments adopted again without change effective March 20, 1992, pursuant to A.R.S. § 41-1026, valid for only 90 days (Supp. 92-1).